50-200 KVA 3:3 | 50KVA
Netcon 50 KVA Online 3-Phase UPS is a high-capacity, fully automated power backup system designed to provide stable, uninterrupted, and clean power to critical systems. Built with advanced true double-conversion technology, it ensures zero transfer time, isolating connected equipment from power fluctuations, surges, and outages. This UPS is the ideal choice for data centers, healthcare facilities, industrial automation, telecommunications, and other mission-critical environments where operational continuity is paramount. With CE and IEC Certification, Netcon UPS guarantees global safety and performance standard.
Netcon 50KVA Online 3-Phase UPS is a powerful, scalable, and energy-efficient backup power solution. With its true double-conversion technology, robust design, and modular scalability, it guarantees uninterrupted power to mission-critical systems. Its energy-efficient design, redundancy features, and advanced battery management make it the preferred choice for industries like IT, healthcare, telecommunications, and manufacturing. Its ability to operate in harsh environments ensures 24/7 uptime, making it a vital component for large-scale infrastructure and critical applications.
| Name | Certificate |
|---|---|
| LVD certificate | View Certificate |
| IEC Test Report | View Certificate |
| IEC certificate | View Certificate |
| CE Certificate | View Certificate |
| INPUT | |
|---|---|
| Frequency Range | 40~70Hz (50/60Hz Auto- Sensing) |
| Power factor | >= 0.99 |
| Generator Input | Input |
| Voltage Range | 138~485Vacfor40% load; 305~485Vac for full-load |
| Nominal Voltage (Vac) | 380/400/4 15Vac (3Ph+N+PE) |
| Harmonic distortion (THDi) | <= 3% Linear load |
| Frequency Protection Range | 50/60Hz±10% |
| Bypass Voltage Range | Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 230V:+20% (Optional+10%,+15%) 240V:+15% (Optional+10%) Min.voltage:-45% (Optional-20%,-30%) |
| OUTPUT | |
| Voltage Range | 380/400/4 15Vac (3Ph+N+PE) |
| Harmonic distortion (THDv) | <= 2% with linear load <= 4% with non linear load |
| Voltage Regulation | ±1% |
| Frequency Range | Line Mode: ± 1%/ ± 2%/ ± 4%/ ± 5%/ ± 10% of the rated frequency (Optional) Battery Mode - (50/60 ±0.2%)Hz |
| Power Factor | 1.0 |
| Crest Factor | 3:1 |
| Overload | AC Mode : Load «110%: last 60min, «125%: last 10min, «150%: last 1min, >150%:turn to bypass immediately By Pass Mode : 135% overload long time; >1000% overload 100ms |
| PHYSICAL | |
| Approx. Dimension (D×W×H) | 250 x 828 x 868 |
| Approx. Net Weight | 80KG |
| BATTERY | |
| Charging current (Max.) | 20A Max. (charge current can be set according to battery capacity installed |
| Battery Voltage | Optional Voltage: ± 180/ ± 192/ ± 204/ ± 216/ ± 228/ ± 240/ ± 252/ ± 264/ ± 276/ ± 288/ ± 300Vdc(30/32/34/36/38/40/42/44/ 46/48/50pcs optional); 360Vdc~600Vdc (30~50pcs, 30pcs default, 36~50pcs output power factor 1.0; 32~34pcs output power factor 0.9; 30pcs output power factor 0.8) |
| ENVIRONMENT | |
| Altitude | <1500m, derating required when>1500m |
| Noise level | <55dB |
| Storage temperature | 250 -550 (No battery) |
| Humidity range | 0-95% (Non condensing) |
| Operating temperature | 0°C~40C |
| EFFICIENCY | |
| Efficiency | Up to 95.5% |
| STANDARDS | |
| Safety | IEC/EN62040-1, IEC/EN62477-1 |
| EMC | IEC/EN62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11) |
| SYSTEM FEATURES | |
| Remote LCD | Support |
| Transfer time | Utility to Battery: 0ms; Utility to Bypass: 0ms |
| Alarm | Overload, utility abnormal, UPS fault, battery low, etc |
| Protection | Short circuit, overload, over temperature, battery low, fan fault alarm |
| Communication | USB, RS232, RS485, parallel port, dry contact, intelligent slot, LBS, SNMP card (Optional), relay card (Optiona) |
| Backfeed protection | Support |