1-3KVA, 1:1 | 2000VA / 1800W
Netcon 2KVA RackMount/Tower Online UPS is a state-of-the-art power protection solution designed to provide continuous, clean, and reliable power for critical devices. Built with True Online Double Conversion Technology, it ensures zero transfer time, making it ideal for sensitive equipment that cannot afford even a momentary power disruption. With CE and IEC Certification, Netcon UPS guarantees global safety and performance standard.
Netcon Online UPS delivers seamless backup power and surge protection for business and commercial equipment. Featuring full digital control, 110–300 Vac input, smart charging, hot-swappable batteries, ECO mode, EPO, generator compatibility, and a versatile LCD with multiple comms options, it keeps your systems safe and running efficiently.
| Name | Certificate |
|---|---|
| LVD Certificate | View Certificate |
| CE certificate | View Certificate |
| EMC Certificate | View Certificate |
| EMC Test Report | View Certificate |
| LVD Test Report | View Certificate |
| MODEL | |
|---|---|
| Capacity | 2000VA / 1800W |
| INPUT | |
| Nominal Voltage (Vac) | 208/220/230/240Vac |
| Power factor | >= 0.9 |
| Voltage Range | 110~300Vac (176~280Vac @ 100% load) |
| OUTPUT | |
| Voltage Regulation | ±1% |
| Harmonic distortion (THDv) | <=3% Linear Load <=5% Non Linear Load |
| Transfer time | AC mode to Bat.mode - 0ms Inverter to Bypass - 4 ms (Typical) |
| Output waveform | Pure Sinewave |
| Voltage Range | 208/220/230/240Vac |
| Power Factor | 0.9 |
| Crest Factor | 3:1 |
| Frequency Range | Line Mode - 46~54Hz or 56~64Hz Battery Mode - (50/60±0.1%)Hz |
| PHYSICAL | |
| Approx. Dimension (D×W×H) | 440 x 600 x 86.5 |
| Approx. Net Weight | 10.5KG |
| BATTERY | |
| Battery Number | 4-6 |
| Charging voltage | 54.8Vdc±1% or 82.2Vdc±1% |
| Typical recharging time | 4 hours (to 90% of full capacity) |
| Charging current (Max.) | 6A/12A |
| Capacity (Standard unit) | 9Ah/12V (7Ah/12V optional) |
| ENVIRONMENT | |
| Operating temperature | 0°C~40°C |
| Altitude | <1500m,derating required when>1500m |
| Noise level | <50dB at 1 Meter |
| Humidity range | 20~95%RH @ 0°C~40°C (Non condensing) |
| Storage temperature | -25°C ~ 55°C |
| EFFICIENCY | |
| AC mode | 91% |
| Battery mode | 87% |
| INDICATORS | |
| LCD Display (LCD version) | Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault |
| LED Display (LED version) | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN62477-1 |
| EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |