Netcon
Compact Series 1:1 - 2KVA Floor Mount External Battery

Compact Series 1:1 - 2KVA Floor Mount External Battery

1-3KVA, 1:1 | 2000VA / 1800W

  • Design : Rack / Tower convertible design 
  • True Online Double Conversion: Zero transfer time for uninterrupted power.
  • Wide Input/Output Range: Input 110~300 Vac; Output 208/220/230/240 Vac.
  • High Output Power Factor : Delivers more usable power (0.9/1.0 PF).
  • Crest factor : 3:1
  • Smart Battery Control: Smart charging, cold start, and hot-swappable batteries.
  • Safeguards : Short-circuits, overheating, battery overcharge and overdischarge etc.
  • Smart Monitoring: LCD display with SNMP, RS232, Relay card, and USB support.
  • High Efficiency: Up to 95% with ECO mode and emergency power-off (EPO).
  • Automatic Bypass  :  Ensures power continuity during UPS failure.
  • True Online Double Conversion: Zero transfer time for uninterrupted power.
  • Global Certifications :  CE , EMC and IEC certified .
Applications: Data Centers & IT, Offices, Industrial, Healthcare, Telecom, Retail, Residential.

Netcon 2KVA Floor Mount Online UPS is a state-of-the-art power protection solution designed to provide continuous, clean, and reliable power for critical devices. Built with True Online Double Conversion Technology, it ensures zero transfer time, making it ideal for sensitive equipment that cannot afford even a momentary power disruption. With CE and IEC Certification,  Netcon  UPS guarantees global safety and performance standard.

Key features include a high output power factor (0.9/1.0), ensuring maximum usable power, and multi-layered protection against overload, short circuits, surges, and fluctuations. The LCD display provides real-time system status, while communication ports (SNMP, RS232, USB) enable remote monitoring and control.Designed for high efficiency (up to 95%), it reduces power consumption and operating costs. The automatic bypass function ensures continuous power in case of UPS failure, while generator compatibility allows smooth operation with generator power.

This UPS is available in both Inbuilt Battery and External Battery configurations. The Inbuilt Battery model is a compact, plug-and-play unit best suited for short backup needs in offices, homes, and POS systems. On the other hand, the External Battery model offers extended backup by allowing the connection of additional battery banks, making it perfect for data centers, telecom, industrial automation, and healthcare environments

Name Certificate
EMC Certificate View Certificate
LVD Certificate View Certificate
EMC Test Report View Certificate
LVD Test Report View Certificate
MODEL
Capacity 2000VA / 1800W
INPUT
Nominal Voltage (Vac) 208/220/230/240Vac
Power factor >=0.99
Voltage Range 110~300Vac (176~280Vac @ 100% load)
OUTPUT
Voltage Regulation ±1%
Harmonic distortion (THDv) <=3% Linear Load <=5% Non Linear Load
Output waveform Pure Sinewave
Transfer time AC mode to Bat.mode - 0ms Inverter to Bypass - 4ms (Typical)
Power Factor 0.9
Crest Factor 3:1
Frequency Range Line mode: 46~54Hz or 56~64Hz Bat. mode - (50/60±0.1%)Hz
Output Transfer Time 0 ms
Voltage Range 208/220/230/240Vac
PHYSICAL
Approx. Net Weight 10 KG
Approx. Dimension (D×W×H) 191 x 460 x 337
BATTERY
Typical recharging time 4 hours (to 90% of full capacity)
Charging current (Max.) 6A/12A
Charging voltage 54.8Vdc±1% or 82.2Vdc±1%
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Battery Number 4,6
ENVIRONMENT
Humidity range 20~95%RH @ 0~40°C (Non condensing)
Noise level <50dB at 1 Meter
Operating temperature 0°C to 40°C
Altitude <1500m, derating required when>1500m
Storage temperature -25°C~55°C
EFFICIENCY
Battery mode 87%
AC mode 90%
INDICATORS
LCD Display (LCD version) Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
LED Display (LED version) Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
OTHERS
Frequency Range 46~54Hz or 56~64Hz
KVA 1-3
FREQUENCY
Frequency range 40~70Hz (50/60Hz Auto-Sensing)