Industrial UPS | 400kVA
Netcon Offers low-frequency systems that ensure compatibility with various loads, providing higher reliability and efficiency Commonly used in critical applications like data centers, medical facilities, and industrial environments, low-frequency UPS features include higher power capacity compared to highfrequency units, greater surge capacity for sudden power demands, improved voltage regulation for stable and clean power supply, and enhanced reliability to withstand harshconditions. These systems are preferred in applications where reliability, capacity, and load compatibility are essential.
| Name | Certificate |
|---|---|
| Note | View Certificate |
| INPUT | |
|---|---|
| Power factor | ≥0.97 |
| Operating frequency range (Hz) | 50/60 (±0.05%) |
| Operating voltage range (Vac) | 380/400/415 Vac (±25% ~ +20%), (3Ph + PE) |
| OUTPUT | |
| Crest factor | 3:1 |
| Efficiency (%) | 93 |
| Output frequency (Hz) | 50/60 (±0.05%) |
| Harmonic distortion (THDv) | ≤1 (Linear load) |
| Output voltage (Vac) | 380/400/415 ac (±1%), (3Ph + N + PE) |
| PHYSICAL | |
| Net weight (kg) | 1640 (6P) /2510 (12P) |
| Shipping weight (kg) | 1770 (6P) / 2665 (12P) |
| Dimension W*D*H (mm) | 1400×1000×1900 (6P) 1640×1000×1900 (12P) |
| ENVIRONMENT | |
| Altitude (m) | <1500 |
| Noise level (dB) | <72 |
| Humidity range (%) | 0 ~ 95 |
| Storage temperature (ºC) | -25 ~ 55 |
| Operating Temperature (ºC) | 0 ~ 40 |
| SYSTEM FEATURES | |
| LED display | Input, Inverter, Bypass, Battery, Output, Status |
| Overload | ≤110%/60min; ≤125%/10min; ≤150%/1min → Bypass |
| Transfer time (ms) | 0 |
| Optional | Harmonic filter, SNMP, LBS cables, battery temperature sensor, bypass current-sharing inductor |
| Communication interface | RS232, RS485, EPO, Dry contact (optional), SNMP (optional) |
| LCD display | I/O voltage, frequency, power, PF, battery status, UPS status, load %, history record |
| Technical | |
| Voltage protection range (%) | Upper: +20% (+10%, +15%, +20% adjustable); Lower: -40% (-10%, -20%, -30%, -40% adjustable) |
| Capacity (kVA/kW) | 400/360 |
| Rated frequency (Hz) | 50/60 (±0.05%) |
| Battery voltage (Vdc) | 384 |
| Rated voltage (Vac) | 380/400/415 Vac, (3Ph + N + PE) |
| Frequency protection range (%) | ±10 % (±2.5%, ±5%, ±10%, ±20% adjustable) |
| STANDARDS | |
| EMC | IEC/EN 62040-2 (IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-8, 61000-4-11, 61000-2-2) |
| Performance | IEC/EN 62040-3 |
| Safety | IEC/EN 62040-1; IEC 62477-1 |