EPOWER Series 3:3 - Transformer Based Industrial UPS

EPOWER Series 3:3 - Transformer Based Industrial UPS

Industrial UPS | 80 kVA

  • Design : Online Double Conversion with full digital control
  • Power Factor (PF) : Output - 0.9, Input - 0.97 with filter
  • Battery : Intelligent management, auto charge, self-test
  • Redundancy : N+X parallel (up to 6 units)
  • Input Range : 380/400/415V (-25% to +20%), 45–65Hz
  • Generator : Power walk-in support
  • Sync : LBS synchronization
  • Protection : Over/under-voltage, overload, short circuit, overheating, etc.
  • EPO : Emergency Power Off switch
  • Interface : LCD/LED, RS232/RS485, MODBUS, SNMP (optional)
  • Back-Feed : Crowbar circuit protection
Applications: Data centers, Medical facilities, and Industrial Environments

Netcon Offers low-frequency systems that ensure compatibility with various loads, providing higher reliability and efficiency Commonly used in critical applications like data centers, medical facilities, and industrial environments, low-frequency UPS features include higher power capacity compared to highfrequency units, greater surge capacity for sudden power demands, improved voltage regulation for stable and clean power supply, and enhanced reliability to withstand harshconditions. These systems are preferred in applications where reliability, capacity, and load compatibility are essential.

Name Certificate
Note View Certificate
INPUT
Operating voltage range (Vac) 380/400/415 Vac (±25% ~ +20%), (3Ph + PE)
Operating frequency range (Hz) 50/60 (±0.05%)
Power factor ≥0.97
OUTPUT
Output voltage (Vac) 380/400/415 Vac (±1%), (3Ph + N + PE)
Efficiency (%) 90.5
Harmonic distortion (THDv) ≤2 (Linear load)
Output frequency (Hz) 50/60 (±0.05%)
Crest factor 3:1
PHYSICAL
Dimension W*D*H (mm) 720×690×1400
Net weight (kg) 450
Shipping weight (kg) 485
ENVIRONMENT
Operating Temperature (ºC) 0 ~ 40
Noise level (dB) <68
Storage temperature (ºC) -25 ~ 55
Humidity range (%) 0 ~ 95
Altitude (m) <1500
SYSTEM FEATURES
Transfer time (ms) 0
Overload ≤110%/60min; ≤125%/10min; ≤150%/1min → Bypass
LCD display I/O voltage, frequency, power, PF, battery status, UPS status, load %, history record
LED display Input, Inverter, Bypass, Battery, Output, Status
Communication interface RS232, RS485, EPO, Dry contact (optional), SNMP (optional)
Optional Harmonic filter, SNMP, LBS cables, battery temperature sensor, bypass current-sharing inductor
Technical
Rated frequency (Hz) 50/60 (±0.05%)
Battery voltage (Vdc) 384
Voltage protection range (%) Upper: +20% (+10%, +15%, +20% adjustable); Lower: -40% (-10%, -20%, -30%, -40% adjustable)
Rated voltage (Vac) 380/400/415 Vac, (3Ph + N + PE)
Capacity (kVA/kW) 80/72
Frequency protection range (%) ±10 % (±2.5%, ±5%, ±10%, ±20% adjustable)
STANDARDS
Performance IEC/EN 62040-3
Safety IEC/EN 62040-1; IEC 62477-1
EMC IEC/EN 62040-2 (IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 61000-4-6, 61000-4-8, 61000-4-11, 61000-2-2)